IEC 60227 05 (BV) 300/500V Single-core Non-sheathed Solid Conductor Cable

APPLICATION
IEC 60227 05 (BV) Single-core Non-sheathed Solid Conductor Cable For Internal Wiring.
IEC 60227 05 of hook up wire is also used in power installation,household electrical appliance,instrument, Telecommunications equipment,switch control,relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
CABLE STANDARDS
IEC 60227,BS,DIN,ICEA up on request.
![]()
BASIC INFORMATION
Code Name
 60227 IEC 05
 Rated Voltage (Uo/U)
 300/500V
 Cable Structure
 CU/PVC Insulation
CONSTRUCTION
Conductor
 Number of conductots:1
 The conductors shall comply with the requirement given in IEC 60228 for class 1
 – class 1 for solid conductors;
 Insulation
 PVC(Polyvinyl Chloride) Type PVC/C according to IEC
CHARACTERISTICS
Conductor temperature
 Maximum conductor temperature in normal use: 70℃
 Installation temperature
 Ambient temperature under installation shall not be below 0℃
 Minimum bending radius
 The bending radius of cable: (D-Diameter of cable)
 D≤25mm——————≥4D
 D>25mm——————≥6D
| Nominal Cross Sectional Area(mm²) | CENELEC Code | NO. of Cores | Class of Conductor | Max.Overall Diameter (mm) | 
|---|---|---|---|---|
| 0.5 | H05V-U | 1 | 1 | 2.3 | 
| 0.75 | H05V-U | 1 | 1 | 2.5 | 
| 1 | H05V-U | 1 | 1 | 2.7 | 